Sign In | Join Free | My himfr.com
Home > High Voltage Test Equipment >

Real Time Monitoring LCD Display 110kV CT Ratio Tester

    Buy cheap Real Time Monitoring LCD Display 110kV CT Ratio Tester from wholesalers
     
    Buy cheap Real Time Monitoring LCD Display 110kV CT Ratio Tester from wholesalers
    • Buy cheap Real Time Monitoring LCD Display 110kV CT Ratio Tester from wholesalers

    Real Time Monitoring LCD Display 110kV CT Ratio Tester

    Ask Lasest Price
    Brand Name : RISING
    Model Number : RSCT-201
    Certification : ISO CE
    Supply Ability : 500 SET PER Month
    Delivery Time : 5-8 days
    • Product Details
    • Company Profile

    Real Time Monitoring LCD Display 110kV CT Ratio Tester

    RSCT-201 High voltage CT Ratio Tester Online

    Product Description

    RSCT-201 high voltage CT conversion ratio tester breaks through the traditional structure and is specially designed and manufactured for online measurement of primary current and secondary current size, conversion ratio, phase difference and polarity judgment of current transformers and transformers below 35kV.The product is composed of primary current clamp (high voltage detector), secondary current clamp, main machine, high voltage insulating rod, monitoring software, communication line, etc. The primary current clamp adopts wireless transmission of test data with a transmission distance of 100 meters.


    Product Features


    1. 1,The product is made up of primary current clamp (high voltage detector), secondary current clamp, main machine, high voltage insulating rod, monitoring software, communication line, etc. The primary current clamp adopts wireless transmission of test data with a transmission distance of 100 meters
    2. 2,The current clamp is made of high performance permalloy alloy with magnetic shielding technology, which is almost unaffected by external magnetic field, ensuring high precision, high stability and high reliability of year-round uninterrupted monitoring
    3. 3,Host LCD display at a glance, at the same time with large storage space, can store 3000 groups of data
    4. 4,The monitoring software has the functions of online real-time monitoring and historical query, dynamic display, maximum, minimum and average value indication, alarm value setting and alarm indication, historical data reading, consulting, saving, printing and other functions
    5. 5,Htct-201 high voltage CT variable ratio tester, at the same time: high and low voltage clamp ammeter, high altitude current tester and other products


    Technical parameters
    Amount of influenceBenchmark conditionsThe working conditions
    The environment temperature23℃±5℃-15℃~50℃
    Environmental humidity40%~60%<70%
    Sine wave distortion≤1%≤3%
    Signal frequencyc50Hz±5Hz45Hz~65Hz
    External electric field, magnetic fieldShould be avoided
    Position of wire under testThe wire under test is in the center of the clamp

    Technical parameters

    function

    High and low voltage current transformer, transformer secondary circuit current, variable ratio test,

    polarity, phase judgment

    The power supplyThe DC6V alkaline dry battery LR03(1.5v AAA×4) worked continuously for 30 hours
    The test wayClip-on CT
    Primary current measurement accuracyrange:0.0A~800A;The resolution of the:0.1A;precision:±0.5%FS
    Accuracy of secondary current testrange:0.00mA~5A;The resolution of the:0.01mA;precision:±0.5%FS
    Variable ratio measurement range1~500
    Variable ratio resolution0.1
    Primary current clamp sizeJaw size:φ48mm;Overall dimensions:76mm×255mm×31mm
    Secondary current clamp sizeJaw size:φ8mm;Overall dimensions:137mm×40mm×19.5mm
    shiftFull automatic shift
    Sampling rate3 times per second
    Data is stored

    3000 sets, press the left arrow key to keep the data and store it automatically (the data will not be lost if the

    power is lost or the battery is changed)

    Keeping data

    Press the left arrow key to HOLD the data, the HOLD symbol is displayed, and then press

    the HOLD key to cancel the HOLD

    Figures refer toPress the right arrow key to enter data lookup mode
    Overflow showsOverrange overflow function: "OL" symbol display
    No signal indication"No signal" is indicated when the host machine does not receive the transmission signal.
    Automatic shutdownAfter about 15 minutes, the meter will shut down automatically
    The battery voltageWhen the battery voltage is lower than 4.8v,“”Display, remind to replace the battery
    Primary current clamp transmission distanceThe wireless transmission distance is 100M

    The connection line of the secondary

    current clamp is long

    2m
    Display modeLCD:128dots×64dots;Backlight function, suitable for dark places
    The LCD sizeAccording to the domain:44mm×27mm
    Size of the host78mm×165mm×42mm
    Instrument quality5kg(including kit and insulating rod)
    Outside interferenceAvoid extremely strong electromagnetic fields;Avoid 433MHz, 315MHz interference with the same frequency
    Operating temperature and humidity-15℃~50℃;70%Rh The following
    Storage temperature and humidity-10℃~60℃;70%Rh The following
    Size of insulating rodφ32mm,1 m/day, 5 day
    Insulated rod withstands pressure110kV
    Dielectric strengthHost and detector: AC1000V/ RMS (between shell and screw)
    Quality Real Time Monitoring LCD Display 110kV CT Ratio Tester for sale
    Inquiry Cart 0
    Send your message to this supplier
     
    *From:
    *To: Wuhan Rising Electric Co., Ltd.
    *Subject:
    *Message:
    Characters Remaining: (0/3000)